Home > Medium Voltage Power Cables > 3.8/6.6kV Copper XLPE insulated Cable
Copper XLPE insulated Cable
Copper XLPE insulated Cable

3.8/6.6kV Copper XLPE insulated Cable

Application

Medium voltage 3.8/6.6kV power cables are designed to be used for the supply of electrical energy in fixed applications up to the rated voltages at a nominal power frequency between 49Hz and 61Hz, they are suitable for use in distribution installation, electrical power station , they are applied for installation, outdoors, underground where subject to mechanical damage.

Construction
  • Conductor: Plain circular compacted copper
  • Conductor Screen: Extruded semi-conducting compound
  • Insulation: XLPE
  • Insulation Screen: Extruded semi-conducting compound
  • Metallic Screen: copper wire
  • Sheath: PVC
Main Characteristics
  • Nominal Voltage: 3.8/6.6 (7.2) kV
  • Maximum Continuous Operating Temperature: 90°C
  • Max. Short Circuit Temperature: 250°C.
Specification

AS/NZS 1429.1:2006Electrie cables-Polymeric insulated Part 1: For working voltages 1.9/3.3 (3.6) kV up to and including 19/33 (36) kV.

Share:

Product Parameters

Sectional Area of Conductor(CU) Nom. Conductor Diameter Nom. Insulation Thickness Nom. Diameter Over insulation Screen Area on Each core Nom. Diameter Over Screened Wires Nom. Overall Diameter Approx. mass
mm² mm mm mm mm² mm mm kg/100m
16 4.8 2.5 11 15.9 12.4 17.9 53
25 5.8 2.5 12 17.6 13.6 19.1 65
35 6.8 2.5 13 17.6 14.5 20 76
50 8 2.5 14.1 17.6 15.6 21.1 90
70 9.6 2.5 15.7 17.6 17.3 22.8 110
95 11.5 2.5 17.6 17.6 18.9 24.4 140
120 13.1 2.5 19.2 17.6 20.5 26 160
150 14.5 2.5 20.6 17.6 21.9 27.4 190
185 16.1 2.5 22.2 17.6 23.5 29.2 230
240 18.5 2.6 24.9 17.6 26.1 31.8 290
300 20.7 2.8 27.6 17.6 29 34.9 350
400 23.6 3 30.9 17.6 32.1 38.2 440

Application and case display

FAQ

How long is the validity period of cold shrink cable accessories?
What is the purpose of a metallic shield in MV and HV cables?
What temperature can high-temperature resistant cables reach, and what are their application scenarios?
What is the length tolerance for cables?
How Do Water-Blocking Cables Work?
How long is the validity period of cold shrink cable accessories?
The validity period for most cold shrink cable accessories is typically 3 years from the date of manufacture, provided they are stored under recommended conditions. These conditions usually include controlled humidity and temperature ranges.
Why do cable prices vary significantly among suppliers within the same region?
Cable prices vary due to differences in supplier strategies, competition, raw materials, and production processes, as well as after-sales services, including installation, equipment, and ongoing support.
Longitudinal Water Blocking vs. Lateral Water Blocking?
A longitudinally water blocking cable is designed with a barrier to prevent the spread of moisture along its length. Longitudinal water blocking stops water from migrating along the cable's core, typically between the conductor strands, insulation layers, or metallic screens. Lateral water blocking ensures that water cannot penetrate the cable in the event that the sheathing is pierced or damaged. Radial water blocking prevents water from penetrating the cable's outer sheath or insulation layers, thereby stopping it from entering the cable structure entirely. Longitudinal water blocking can be achieved through various methods, including the application of water-blocking tapes and powders. These are frequently located on either side of a metallic screen and conductor. Lateral water blocking is typically accomplished by applying a layer of aluminum/polyester tape to the underside of the outer sheath.
What is the minimum order quantity for the product?
The minimum order quantity for low and medium voltage cables is 200 meters, whereas for high voltage cables, it is 2000 meters. Should the order quantity fall below the MOQ, however, if the factory has stock, we can still supply it.
What are the benefits of EPR material?
EPR is widely used as an insulation material for electric cables due to its high dielectric strength, and it also serves as a sheathing material with excellent ozone and weathering resistance. EPR has a wide thermal range, typically spanning from -55°C to 150°C. Unlike other organic rubbers, there is no need to tin the copper conductor to prevent deterioration of the rubber.

Get in Touch With Our Team

We're here to answer any questions you may have about our products, services, or technical specifications.
Address: No. 1207, Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou, China

    your Name

    *

    your Email

    *

    your Phone

    your Whatsapp

    *

    Country

    Products&service

    Message

    *



    +86 371-63395670
    info@starsunelectric.com
    +86 19137160160
    Engineered for Excellence, Certified for Reliability – Power Cables That Meet IEC, ANATEL & INMETRO Standards Globally



      X