Medium voltage 6.35/11kV power cables are designed to be used for the supply of electrical energy in fixed applications up to the rated voltages at a nominal power frequency between 49Hz and 61Hz., they are suitable for use in distribution installation, electrical power station , they are applied for installation, outdoors, underground where subject to mechanical damage.
AS/NZS 1429.1:2006 Electric cables-Polymeric insulated Part 1: For working voltages 1.9/3.3 (3.6) kV up to and including 19/33 (36) kV.
| No.of Cores and Nominal Cross Section(AL) | Nom. Conductor Diameter | Nom. Insulation Thickness | Nom. Diameter Over insulation | Screen Area on Each core | No. and Diameter of Screened Wires | Nom. Diameter Over Screened Wires | Nom. Overall Diameter | Approx. Mass |
| mm² | mm | mm | mm | mm² | no x mm | mm | mm | kg/100m |
| 3×35 | 6.9 | 3.4 | 14.9 | 6.8 | 12 x 0.85 | 16.3 | 43.9 | 153 |
| 3×50 | 8.1 | 3.4 | 16 | 6.8 | 12 x 0.85 | 17.5 | 46.7 | 175 |
| 3×70 | 9.6 | 3.4 | 17.6 | 7.4 | 13 x 0.85 | 19 | 50.4 | 211 |
| 3×95 | 11.4 | 3.4 | 19.3 | 7.9 | 14 x 0.85 | 20.7 | 54.2 | 251 |
| 3×120 | 12.8 | 3.4 | 20.7 | 8.5 | 15 x 0.85 | 22.1 | 57.5 | 289 |
| 3×150 | 14.2 | 3.4 | 22.1 | 8.5 | 15 x 0.85 | 23.5 | 60.7 | 326 |
| 3×185 | 15.7 | 3.4 | 23.6 | 9.6 | 17 x 0.85 | 25.2 | 64.6 | 379 |
| 3×240 | 18 | 3.4 | 25.9 | 10.2 | 18 x 0.85 | 27.6 | 70.2 | 459 |
| 3×300 | 20.1 | 3.4 | 28.3 | 10.8 | 19 x 0.85 | 29.6 | 74.7 | 535 |
| 3×400 | 23 | 3.4 | 31.1 | 11.9 | 21 x 0.85 | 32.7 | 82.3 | 655 |