Home > Overhead Conductors > AAC – All Aluminum Conductors ASTM B 231
AAC
AAC

AAC – All Aluminum Conductors ASTM B 231

Application

Classes AA and A are used primarily for overhead transmission and primary and secondary distribution, where ampacity must be maintained and a lighter conductor (compared to ACSR) is desired, and when conductor strength is not a critical factor. Classes B and C are used primarily as bus, apparatus connectors and jumpers, where additional flexibility is required.

Specifications
  • ASTM B 231 Concentric-Lay-Stranded Aluminum 1350 Conductors.

Note:We also can produce based on other international standards, such as IEC、ASTM、AS  etc.

Construction

Hard-Drawn aluminum wires, concentrically stranded

Share:

Product Parameters

Code name Area Number of wires Diameter of wire Approx. Overall diameter Unit weight Nominal breaking load Nom. DC resistance at 20 deg.
Nominal Actual
AWG or MCM mm2 No. mm mm kg/km kN ohm/km
Peachbell 6 13.3 7 1.56 4.68 36.6 2.53 2.1606
Rose 4 21.1 7 1.96 5.88 58.2 3.91 1.3619
Iris 2 33.6 7 2.47 7.41 92.6 5.99 0.855
Pansy 1 42.4 7 2.78 8.34 116.6 7.3 0.6779
Poppy 1/0 53.5 7 3.12 9.36 147.2 8.84 0.5373
Aster 2/0 67.4 7 3.5 10.5 185.7 11.1 0.4262
Phlox 3/0 85 7 3.93 11.79 233.9 13.5 0.3379
Oxlip 4/0 107.2 7 4.42 13.26 295.2 17 0.268
Valerian 250 126.7 19 2.91 14.55 348.6 20.7 0.2268
Sneezewort 250 126.7 7 4.8 14.4 348.8 20.1 0.2268
Laurel 266.8 135.2 19 3.01 15.05 372.2 22.1 0.2126
Daisy 266.8 135.2 7 4.96 14.88 372.3 21.4 0.2126
Peony 300 152 19 3.19 15.95 418.3 24.3 0.189
Tulip 336.4 170.5 19 3.38 16.9 469.5 27.3 0.1686
Daffodil 350 177.3 19 3.45 17.25 487.9 28.4 0.1621
Canna 397.5 201.4 19 3.67 18.35 554.9 31.6 0.1427
Goldentuft 450 228 19 3.91 19.55 627.6 35 0.126
Syringa 477 241.7 37 2.88 20.16 664.8 38.6 0.1189
Cosmos 477 241.7 19 4.02 20.1 664.8 37 0.1189
Hyacinth 500 253.3 37 2.95 20.65 696.8 40.5 0.1134
Zinnia 500 253.3 19 4.12 20.6 697.1 38.9 0.1134
Mistletoe 556.5 282 37 3.12 21.84 775.7 44.3 0.1019
Dahlia 556.5 282 19 4.35 21.75 775.8 43.3 0.1019
Meadowsweet 600 304 37 3.23 22.61 836.3 47.5 0.0945
Orchid 636 322.3 37 3.33 23.31 886.9 50.4 0.0892
Heuchera 650 329.4 37 3.37 23.59 907.4 51.7 0.0872
Flag 700 354.7 61 2.72 24.48 975.8 57.1 0.081
Verbena 700 354.7 37 3.49 24.43 975.7 55.4 0.081
Nasturtium 715.5 362.6 61 2.75 24.75 998.5 58.4 0.0793
Violet 715.5 362.6 37 3.53 24.71 998.5 56.7 0.0793
Cattail 750 380 61 2.82 25.38 1046 60.3 0.0756
Petunia 750 380 37 3.62 25.34 1046 58.6 0.0756
Lilac 795 402.8 61 2.9 26.1 1110 63.8 0.0713
Arbutus 795 402.8 37 3.72 26.04 1109 61.8 0.0713
Snapdragon 900 456 61 3.09 27.81 1256 70.8 0.063
Cockscomb 900 456 37 3.96 27.72 1256 68.4 0.063
Goldenrod 954 483.4 61 3.18 28.62 1331 75 0.0594
Magnolia 954 483.4 37 4.08 28.56 1331 72.6 0.0594
Camellia 1000 506.7 61 3.25 29.25 1394 78.3 0.0567
Hawkweed 1000 506.7 37 4.18 29.26 1395 76.2 0.0567
Larkspur 1033.5 523.7 61 3.31 29.79 1442 81.3 0.0549
Bluebell 1033.5 523.7 37 4.25 29.75 1441 78.8 0.0549
Marigold 1113 564 61 3.43 30.87 1553 87.3 0.0509
Hawthorn 1192.5 604.2 61 3.55 31.95 1662 93.5 0.0476
Narcissus 1272 644.5 61 3.67 33.03 1774 98.1 0.0446
Columbine 1351 684.6 61 3.78 34.02 1884 104 0.042
Carnation 1431 725.1 61 3.89 35.01 1997 108 0.0396
Gladiolus 1510.5 765.4 61 4 36 2108 114 0.0375
Coreopsis 1590 805.7 61 4.1 36.9 2216 120 0.0357
Jessamine 1750 886.7 61 4.3 38.7 2442 132 0.0324
Cowslip 2000 1013 91 3.77 41.47 2787 153 0.0284
Sagebrush 2250 1140 91 3.99 43.89 3166 167 0.0255
Lupine 2500 1267 91 4.21 46.31 3519 186 0.0229
Bitterroot 2750 1393 91 4.42 48.62 3872 205 0.0208
Trillium 3000 1520 127 3.9 50.7 4226 223 0.0191
Bluebonnet 3500 1773 127 4.22 54.86 4977 261 0.0165

Application and case display

FAQ

What is the validity period for the offer of cable?
What is the service life of cables?
What is the minimum order quantity for the product?
What is the length tolerance for cables?
How do you calculate the minimum bending radius of cables?
What is the validity period for the offer of cable?
Typically, the offer is valid for 7 to 30 days, and the price will be adjusted according to the cost of raw materials and the exchange rate.
What is the service life of cables?
The design life of power cables is typically 20 to 30 years; however, this can vary significantly based on factors such as installation, environmental conditions, and the quality of the cable.
What is the minimum order quantity for the product?
The minimum order quantity for low and medium voltage cables is 200 meters, whereas for high voltage cables, it is 2000 meters. Should the order quantity fall below the MOQ, however, if the factory has stock, we can still supply it.
What is the length tolerance for cables?
The tolerance for the power cable is 0 to +0.5%. For the bare conductor, the tolerance is ±5%.
How do you calculate the minimum bending radius of cables?
The bend radius refers to the curved shape in which an electrical cable can be bent or curved without sustaining damage. To determine the minimum bend radius for cables, apply the following formula: Minimum Bend Radius = Cable Outer Diameter×Cable Multiplier. For example, if the outer diameter of a cable is 20mm, its minimum bending radius would be 20mm×6 = 120mm. Conversely, if an armored cable has an outer diameter of 30mm, its minimum bending radius would be 30mm×12 = 360mm.

Get in Touch With Our Team

We're here to answer any questions you may have about our products, services, or technical specifications.
Address: No. 1207, Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou, China

    your Name

    your Email

    *

    Company Name

    *

    Country

    your Phone

    *

    WhatsApp No.

    Message

    *



    +86 371-63395670
    info@starsunelectric.com