Home > Medium Voltage Power Cables > FR-N20XA8E-AR Triplex 12/20 (24) kV NFC 33-226 Cable
FR-N20XA8E-AR Triplex 12/20 (24) KV NFC 33-226 Cable
FR-N20XA8E-AR Triplex 12/20 (24) KV NFC 33-226 Cable

FR-N20XA8E-AR Triplex 12/20 (24) kV NFC 33-226 Cable

Application

FR-N20XA8E-AR Triplex cables are the new generation of cables for public medium voltage distribution. Used for direct installation on the ground, outdoors, indoors and in cable ducts.

Construction
  • Conductor: Aluminum, class 2, circular compacted conductors
  • Conductor screen: Non-metallic, semi-conducting compound
  • Insulation: Cross-linked polyethylene (XLPE)
  • Insulation screen: Non-metallic, semi-conducting compound, extruded strippable grooved elastomer
  • Longitudinal water blocking: Swelling powder
  • Metallic screen: Aluminium plastic tape (AL/PET)
  • Outer sheath: Polyethylene (PE)
Main Characteristics
  • Maximum conductor temperature in normal operation: 90℃ .
  • Short circuit temperature (5 seconds maximum duration): Shall not exceed 250℃ .
  • Ambient installation temperature range: -10~50℃ .
  • Weather resistance: AN3/AF2
  • Flame retardant: C2, NFC 32-070
  • Water proof: AD8
  • Mechanical resistance to impacts: AG4
  • Minimum bending radius: During installation: 15D   After installation: 10D (Note: D is overall diameter of cable)
Main Specification

IEC 60228 Conductors of insulated cables
NFC 33-226 Cables isolés et leurs accessoires pour réseaux d’énergie Câbles de tensions assignées comprises entre 6/10 (12) kV et 18/30 (36) kV, isoles au polyéthylene réticulé à gradient fixé, pour réseaux de distribution
IEC 60502-2 Power cables with extruded insulation and their accessories for rated voltages from 1kV (Um=1.2KV) up to 30kV (Um=36KV) – Part 2: Cables for rated voltages of 6kV (Um=7.2KV) and 30kV (Um=36kV)

Share:

Product Parameters

No.of Cores and Nominal Cross Section Min.Number of Wires Nominal Insulation Thickness Nominal AL/PET Tape Thickness Nominal Sheath Thickness Approx. Overall Diameter Approx. Weight Max.DC Resistance of Conductor at 20℃
mm² No. mm mm mm mm kg/km Ω/km
3×1×50 6 5.5 0.20 2.0 59.8 2223 0.641
3×1×70 12 5.5 0.20 2.0 63.5 2560 0.443
3×1×95 15 5.5 0.20 2.0 67.4 2949 0.320
3×1×120 15 5.5 0.20 2.0 70.0 3263 0.253
3×1×150 15 5.5 0.20 2.0 73.2 3626 0.206
3×1×185 30 5.5 0.20 2.0 76.9 4090 0.164
3×1×240 30 5.5 0.20 2.1 82.3 4834 0.125
3×1×300 30 5.5 0.20 2.2 87.5 5602 0.100
3×1×400 53 5.5 0.20 2.3 93.7 6629 0.0778
3×1×500 53 5.5 0.20 2.4 101.7 7927 0.0605
3×1×630 53 5.5 0.20 2.5 110.2 9533 0.0469

Application and case display

FAQ

What is the service life of cables?
How long is the validity period of cold shrink cable accessories?
Why are low-smoke zero-halogen materials developed for cables?
What is the validity period for the offer of cable?
What is the application of Armored vs. Unarmored Cables?
What is the service life of cables?
The design life of power cables is typically 20 to 30 years; however, this can vary significantly based on factors such as installation, environmental conditions, and the quality of the cable.
How long is the validity period of cold shrink cable accessories?
The validity period for most cold shrink cable accessories is typically 3 years from the date of manufacture, provided they are stored under recommended conditions. These conditions usually include controlled humidity and temperature ranges.
Why are low-smoke zero-halogen materials developed for cables?
Halogen-containing flame-retardant materials can produce a large amount of harmful substances during combustion. Low-smoke zero-halogen flame-retardant materials are developed to reduce this risk and meet environmental and flame-retardant requirements.
What is the validity period for the offer of cable?
Typically, the offer is valid for 7 to 30 days, and the price will be adjusted according to the cost of raw materials and the exchange rate.
What is the application of Armored vs. Unarmored Cables?
Armored cables are suitable for use in hazardous environments, such as underground installations, areas with high moisture levels, and areas prone to mechanical damage. Unarmored cables are suitable for less demanding applications, such as inside walls or other protected locations.

Get in Touch With Our Team

Contact us for product information, cable selection, and project support.
Address: No. 1207 , Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou City, China

    your Name

    your Email

    *

    Company Name

    *

    Country

    your Phone

    *

    WhatsApp No.

    Message

    *

    +86 371-63395670
    [email protected]
    +86 13938540747
    Engineered for Excellence, Certified for Reliability – Power Cables That Meet IEC, ANATEL & INMETRO Standards Globally

      X