Home > Control Cables > KVVP PVC insulated Copper wire shielded Control Cable
KVVP Control Cable
KVVP Control Cable

KVVP PVC insulated Copper wire shielded Control Cable

Application

KVVP Control Cable is applicable to control,monitoring circuit and protection circuit with AC rated voltage (0.6/1kV)or below.

Construction
  • Conductor: Copper,class 1,2,or 5,solid,stranded round or soft conductor
  • Insulation: Polyvinyl chloride (PVC)
  • Filler: Non-hygroscopic material
  • Binder: Non-hygroscopic material
  • Metallic screen: Copper wire braid
  • Outer sheath: Polyvinyl chloride (PVC)
Main Characteristics
  • Good electrical and mechanical properties.Resistance to abrasion,moisture and sunlight.
    Adequate resistance to oil and abrasion.
Specification

IEC 60228 Conductors of Insulated Cables.
IEC 60502-1 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2kV)up to 30kV(Um=36kV)-Part 1:Cables for Rated Voltages of 1kV(Um=1.2kV) and 3kV(Um=3.6kV).

Share:

Product Parameters

No. × section Insulation
thickness
Average  diameter Min.insulation
resistance
Conductor resistance at 20℃
Solid conductor Stranded conductor
Min. Max Min. Max Solid conductor Stranded  conductor Solid conductor Stranded  conductor
mm² mm mm mm mm mm MΩ*km MΩ*km Ω/km Ω/km
2×0.75 0.6 7.7 9.3 7.9 9.6 0.012 0.014 24.0 24.5
2×1.0 0.6 8.0 9.7 8.2 9.9 0.011 0.013 18.1 18.1
2×1.5 0.7 8.9 10.7 9.1 11.0 0.011 0.010 12.1 12.1
2×2.5 0.8 10.0 12.1 10.2 12.4 0.010 0.009 7.41 7.41
2×4 0.8 10.9 13.2 11.2 13.5 0.0085 0.0077 4.61 4.61
2×6 0.8 11.9 14.3 12.8 15.5 0.0070 0.0065 3.08 3.08
2×10 1.0 15.6 18.8 0.0065 1.83
3×0.75 0.6 8.1 9.7 8.3 10.0 0.012 0.014 24.0 24.5
3×1.0 0.6 8.4 10.1 8.6 10.4 0.011 0.013 18.1 18.1
3×1.5 0.7 9.3 11.2 9.5 11.5 0.011 0.010 12.1 12.1
3×2.5 0.8 10.5 12.7 10.8 13.0 0.010 0.009 7.41 7.41
3×4 0.8 11.5 13.9 11.8 14.2 0.0085 0.0077 4.61 4.61
3×6 0.8 13.1 15.8 13.7 16.6 0.0070 0.0065 3.08 3.08
3×10 1.0 16.4 19.9 0.0065 1.83
4×0.75 0.6 8.6 10.4 8.8 10.7 0.012 0.014 24.0 24.5
4×1.0 0.6 8.9 10.8 9.2 11.1 0.011 0.013 18.1 18.1
4×1.5 0.7 10.0 12.1 10.2 12.4 0.011 0.010 12.1 12.1
4×2.5 0.8 11.4 13.8 11.6 14.0 0.010 0.009 7.41 7.41
4×4 0.8 13.0 15.7 13.6 16.4 0.0085 0.0077 4.61 4.61
4×6 0.8 14.4 17.4 14.9 18.0 0.0070 0.0065 3.08 3.08
4×10 1.0 17.9 21.6 0.0065 1.83
5×0.75 0.6 9.2 11.1 9.4 11.4 0.012 0.014 24.0 24.5
5×1.0 0.6 9.6 11.6 9.8 11.9 0.011 0.013 18.1 18.1
5×1.5 0.7 10.7 13.0 11.0 13.3 0.011 0.010 12.1 12.1
5×2.5 0.8 12.9 15.5 13.1 15.9 0.010 0.009 7.41 7.41
5×4 0.8 14.3 17.2 14.7 17.7 0.0085 0.0077 4.61 4.61
5×6 0.8 15.6 18.8 16.1 19.4 0.0070 0.0065 3.08 3.08
5×10 1.0 19.8 24.0 0.0065 1.83
7×0.75 0.6 9.8 11.8 10.1 12.2 0.012 0.014 24.0 24.5
7×1.0 0.6 10.2 12.4 10.5 12.7 0.011 0.013 18.1 18.1
7×1.5 0.7 11.5 13.9 11.8 14.3 0.011 0.010 12.1 12.1
7×2.5 0.8 14.1 17.0 14.4 17.3 0.010 0.009 7.41 7.41
7×4 0.8 15.4 18.6 15.8 19.1 0.0085 0.0077 4.61 4.61
7×6 0.8 16.8 20.3 17.4 21.0 0.0070 0.0065 3.08 3.08
7×10 1.0 21.5 26.0 0.0065 1.83
8×0.75 0.6 10.7 13.0 11.1 13.4 0.012 0.014 24.0 24.5
8×1.0 0.6 11.2 13.6 11.5 14.0 0.011 0.013 18.1 18.1
8×1.5 0.7 13.5 16.3 13.9 16.7 0.011 0.010 12.1 12.1
8×2.5 0.8 15.5 18.7 15.8 19.1 0.010 0.009 7.41 7.41
8×4 0.8 17.0 20.5 17.5 21.1 0.0085 0.0077 4.61 4.61
8×6 0.8 19.0 23.0 19.7 23.8 0.0070 0.0065 3.08 3.08
8×10 1.0 24.2 29.3 0.0065 1.83
10×0.75 0.6 11.9 14.3 12.8 15.5 0.012 0.014 24.0 24.5
10×1.0 0.6 13.0 15.7 13.6 16.5 0.011 0.013 18.1 18.1
10×1.5 0.7 15.0 18.1 15.4 18.6 0.011 0.010 12.1 12.1
10×2.5 0.8 17.3 20.9 17.7 21.3 0.010 0.009 7.41 7.41
10×4 0.8 19.4 23.4 20.0 24.1 0.0085 0.0077 4.61 4.61
10×6 0.8 21.3 25.8 22.1 26.7 0.0070 0.0065 3.08 3.08
10×10 1.0 27.9 33.7 0.0065 1.83
12×0.75 0.6 12.8 15.4 13.2 15.9 0.012 0.014 24.0 24.5
12×1.0 0.6 13.6 16.4 14.0 16.9 0.011 0.013 18.1 18.1
12×1.5 0.7 15.4 18.6 15.8 19.1 0.011 0.010 12.1 12.1
12×2.5 0.8 17.8 21.5 18.2 22.0 0.010 0.009 7.41 7.41
12×4 0.8 20.0 24.1 20.6 24.9 0.0085 0.0077 4.61 4.61
12×6 0.8 22.0 26.6 22.8 27.5 0.0070 0.0065 3.08 3.08
14×0.75 0.6 13.5 16.3 13.9 16.8 0.012 0.014 24.0 24.5
14×1.0 0.6 14.2 17.1 14.6 17.6 0.011 0.013 18.1 18.1
14×1.5 0.7 16.1 19.4 16.5 19.9 0.011 0.010 12.1 12.1
14×2.5 0.8 19.0 22.9 19.4 23.4 0.010 0.009 7.41 7.41
14×4 0.8 20.9 25.2 21.5 26.0 0.0085 0.0077 4.61 4.61
14×6 0.8 23.0 27.8 24.1 29.1 0.0070 0.0065 3.08 3.08
16×0.75 0.6 14.1 17.1 14.6 17.6 0.012 0.014 24.0 24.5
16×1.0 0.6 14.8 17.9 15.2 18.4 0.011 0.013 18.1 18.1
16×1.5 0.7 16.8 20.3 17.3 20.9 0.011 0.010 12.1 12.1
16×2.5 0.8 19.9 24.1 20.4 24.6 0.010 0.009 7.41 7.41
19×0.75 0.6 14.7 17.8 15.2 18.4 0.012 0.014 24.0 24.5
19×1.0 0.6 15.5 18.7 15.9 19.3 0.011 0.013 18.1 18.1
19×1.5 0.7 17.6 21.3 18.1 21.9 0.011 0.010 12.1 12.1
19×2.5 0.8 20.9 25.2 21.4 25.8 0.010 0.009 7.41 7.41
24×0.75 0.6 16.8 20.3 17.4 21.0 0.012 0.014 24.0 24.5
24×1.0 0.6 17.7 21.3 18.2 22.0 0.011 0.013 18.1 18.1
24×1.5 0.7 20.6 24.9 21.2 25.6 0.011 0.010 12.1 12.1
24×2.5 0.8 24.3 29.4 24.9 30.1 0.010 0.009 7.41 7.41
27×0.75 0.6 17.1 20.7 17.7 21.4 0.012 0.014 24.0 24.5
27×1.0 0.6 18.0 21.7 19.0 22.9 0.011 0.013 18.1 18.1
27×1.5 0.7 21.0 25.4 21.6 26.1 0.011 0.010 12.1 12.1
27×2.5 0.8 24.8 30.0 25.4 30.7 0.010 0.009 7.41 7.41
30×0.75 0.6 17.6 21.3 18.3 22.1 0.012 0.014 24.0 24.5
30×1.0 0.6 19.6 22.9 19.6 23.6 0.011 0.013 18.1 18.1
30×1.5 0.7 21.7 26.2 22.3 27.0 0.011 0.010 12.1 12.1
30×2.5 0.8 25.7 31.0 26.3 31.7 0.010 0.009 7.41 7.41
37×0.75 0.6 19.2 23.3 19.9 24.1 0.012 0.014 24.0 24.5
37×1.0 0.6 20.3 24.5 20.9 25.3 0.011 0.013 18.1 18.1
37×1.5 0.7 23.3 28.1 24.2 29.2 0.011 0.010 12.1 12.1
37×2.5 0.8 28.1 34.0 28.8 34.8 0.010 0.009 7.41 7.41
44×0.75 0.6 21.3 25.8 22.1 26.7 0.012 0.014 24.0 24.5
44×1.0 0.6 22.5 27.1 23.2 28.1 0.011 0.013 18.1 18.1
44×1.5 0.7 26.2 31.5 26.8 32.1 0.011 0.010 12.1 12.1
44×2.5 0.8 31.6 38.0 32.2 38.6 0.010 0.009 7.41 7.41
48×0.75 0.6 21.9 26.0 22.5 26.6 0.012 0.014 24.0 24.5
48×1.0 0.6 22.8 28.5 23.4 29.1 0.011 0.013 18.1 18.1
48×1.5 0.7 26.8 32.0 27.4 32.6 0.011 0.010 12.1 12.1
48×2.5 0.8 32.2 38.5 32.8 39.1 0.010 0.009 7.41 7.41
52×0.75 0.6 22.6 38.2 23.2 38.8 0.012 0.014 24.0 24.5
52×1.0 0.6 23.7 28.3 24.3 28.9 0.011 0.013 18.1 18.1
52×1.5 0.7 28.3 33.6 28.9 34.2 0.011 0.010 12.1 12.1
52×2.5 0.8 33.7 40.0 34.3 40.6 0.010 0.009 7.41 7.41
61×0.75 0.6 23.7 28.3 24.3 28.9 0.012 0.014 24.0 24.5
61×1.0 0.6 24.7 30.2 25.3 30.8 0.011 0.013 18.1 18.1
61×1.5 0.7 29.7 35.6 30.3 36.2 0.011 0.010 12.1 12.1
61×2.5 0.8 35.6 42.0 36.2 42.6 0.010 0.009 7.41 7.41

Application and case display

FAQ

What is the application of Armored vs. Unarmored Cables?
How long is the validity period of cold shrink cable accessories?
What is the minimum order quantity for the product?
What are the weight limits for different types of packages?
Why do cable prices vary significantly among suppliers within the same region?
How do you calculate the minimum bending radius of cables?
The bend radius refers to the curved shape in which an electrical cable can be bent or curved without sustaining damage. To determine the minimum bend radius for cables, apply the following formula: Minimum Bend Radius = Cable Outer Diameter×Cable Multiplier. For example, if the outer diameter of a cable is 20mm, its minimum bending radius would be 20mm×6 = 120mm. Conversely, if an armored cable has an outer diameter of 30mm, its minimum bending radius would be 30mm×12 = 360mm.
What is the length tolerance for cables?
The tolerance for the power cable is 0 to +0.5%. For the bare conductor, the tolerance is ±5%.
Flame Retardant Cables VS Fire Resistant Cables?
Both types of cables are crucial in enhancing the likelihood of escape and survival in the event of a fire and are often confused with one another. However, there is a fundamental distinction between flame retardant cables and fire resistant cables. Flame retardant cables are engineered to inhibit the spread of fire to adjacent areas. On the other hand, fire resistant cables are specifically designed to preserve circuit integrity and ensure functionality during a fire, under specified conditions, aiding both evacuees and firefighters.
What are the benefits of EPR material?
EPR is widely used as an insulation material for electric cables due to its high dielectric strength, and it also serves as a sheathing material with excellent ozone and weathering resistance. EPR has a wide thermal range, typically spanning from -55°C to 150°C. Unlike other organic rubbers, there is no need to tin the copper conductor to prevent deterioration of the rubber.
Longitudinal Water Blocking vs. Lateral Water Blocking?
A longitudinally water blocking cable is designed with a barrier to prevent the spread of moisture along its length. Longitudinal water blocking stops water from migrating along the cable's core, typically between the conductor strands, insulation layers, or metallic screens. Lateral water blocking ensures that water cannot penetrate the cable in the event that the sheathing is pierced or damaged. Radial water blocking prevents water from penetrating the cable's outer sheath or insulation layers, thereby stopping it from entering the cable structure entirely. Longitudinal water blocking can be achieved through various methods, including the application of water-blocking tapes and powders. These are frequently located on either side of a metallic screen and conductor. Lateral water blocking is typically accomplished by applying a layer of aluminum/polyester tape to the underside of the outer sheath.

Get in Touch With Our Team

We're here to answer any questions you may have about our products, services, or technical specifications.
Address: No. 1207, Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou, China