N2XSEBY Three core 18/30 (36) kV Copper XLPE insulated Steel tape armored Cable

Application

Medium voltage N2XSEBY cables for distribution networks.They are suitable for laying indoor,tunnel,cables trench and underground,it is able to bear external mechanical forces,but unable to bear heavy pulling force,it widely used in transformer stations,electric power plants and industrial plants.

Construction
  • Conductor: Copper,class 2,circular compacted conductors
  • Conductor screen: Non-metallic,semi-conducting compound
  • Insulation: Cross -linked polyethylene(XLPE)
  • Insulation screen: Non-metallic,semi-conducting compound
  • Metallic screen: Copper tape
  • Filler: Non -hygroscopic material
  • Inner sheath: Polyvinyl chloride(PVC)
  • Armour: Steel tape
  • Outer sheath: Polyvinyl chloride(PVC)
Main Characteristics
  • Good electrical and mechanical properties.
  • Minimal dielectric loss,high insulation resistance.
Specification

IEC 60228 Conductors of Insulated Cables
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2kV) up to 30kV (Um=36kV)-Part 2: Cables for Rated Voltages from 6kV (Um=7.2kV) up to 30kV (Um=36kV).

Share:

Product Parameters

No.of Cores and Nominal Cross Section Nominal Insulation Thickness Nominal Steel Tape Thickness Nominal Sheath Thickness Approx. Overall Diameter Approx.Weight Max.D.C. Resistance of Conductor at 20℃
Cu Al Cu Al
mm² mm mm mm mm kg/km kg/km Ω/km Ω/km
3×50 8.0 0.5 3.3 72 5980 5117 0.387 0.641
3×70 8.0 0.5 3.4 76.1 6955 5707 0.268 0.443
3×95 8.0 0.5 3.5 80.1 8064 6333 0.193 0.32
3×120 8.0 0.8 3.7 84.5 9939 7749 0.153 0.253
3×150 8.0 0.8 3.8 88 11095 8389 0.124 0.206
3×185 8.0 0.8 3.9 92 12588 9179 0.0991 0.164
3×240 8.0 0.8 4.1 97.6 14742 10319 0.0754 0.125
3×300 8.0 0.8 4.2 102.8 17120 11576 0.0601 0.100
3×400 8.0 0.8 4.5 109.4 20299 13157 0.047 0.0778
3×500 8.0 0.8 4.7 117.5 24271 15204 0.0366 0.0605
3×630 8.0 0.8 4.9 126.3 29231 17459 0.0283 0.0469

Application and case display

FAQ

What is the length tolerance for cables?
How do you calculate the minimum bending radius of cables?
What are the benefits of EPR material?
What is the purpose of a metallic shield in MV and HV cables?
Is a flame-retardant cable also fire resistant?
What is the length tolerance for cables?
The tolerance for the power cable is 0 to +0.5%. For the bare conductor, the tolerance is ±5%.
How do you calculate the minimum bending radius of cables?
The bend radius refers to the curved shape in which an electrical cable can be bent or curved without sustaining damage. To determine the minimum bend radius for cables, apply the following formula: Minimum Bend Radius = Cable Outer Diameter×Cable Multiplier. For example, if the outer diameter of a cable is 20mm, its minimum bending radius would be 20mm×6 = 120mm. Conversely, if an armored cable has an outer diameter of 30mm, its minimum bending radius would be 30mm×12 = 360mm.
What are the benefits of EPR material?
EPR is widely used as an insulation material for electric cables due to its high dielectric strength, and it also serves as a sheathing material with excellent ozone and weathering resistance. EPR has a wide thermal range, typically spanning from -55°C to 150°C. Unlike other organic rubbers, there is no need to tin the copper conductor to prevent deterioration of the rubber.
What is the purpose of a metallic shield in MV and HV cables?
Medium and high voltage power cables, typically those in circuits exceeding 2kV, usually feature a shield layer made of copper or aluminum tape. Similar to their use in low voltage cables, metallic wires and tapes are employed to prevent electromagnetic interference. These shields effectively neutralize or significantly diminish the field currents surrounding the conductor or core. The capacitive and inductive charging currents induced under normal operating conditions are subsequently grounded by the metallic screen.
Is a flame-retardant cable also fire resistant?
No. A flame-retardant cable is not the same as a fire-resistant cable. A flame-retardant cable is designed to restrict the spread of fire by inhibiting combustion. Fire-resistant cables, on the other hand, maintain circuit integrity and continue to function for a specified time under defined fire conditions.

Get in Touch With Our Team

Contact us for product information, cable selection, and project support.
Address: No. 1207 , Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou City, China

    your Name

    your Email

    *

    Company Name

    *

    Country

    your Phone

    *

    WhatsApp No.

    Message

    *

    +86 371-63395670
    [email protected]
    +86 13938540747
    Engineered for Excellence, Certified for Reliability – Power Cables That Meet IEC, ANATEL & INMETRO Standards Globally

      X