Medium voltage N2XSEY cables for distribution networks;also for connection to generation units and plant and process connection.To be laid directly in ground,outdoors,indoors and in cable ducts.
IEC60228 Conductors of Insulated Cables
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV)up to 30kV(Um=36KV)-Part 2:Cables for Rated Voltages of 6kV(Um=7.2KV)up to 30kV (Um=36kV)
| No.of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight | Max.D.C.Resistance of Conductor at 20℃ | ||
| Cu | Al | Cu | Al | ||||
| mm² | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 3×35 | 5.5 | 2.7 | 56.1 | 3199 | 2562 | 0.524 | 0.868 |
| 3×50 | 5.5 | 2.8 | 58.7 | 3675 | 2811 | 0.387 | 0.0641 |
| 3×70 | 5.5 | 2.9 | 62.6 | 4449 | 3201 | 0.268 | 0.443 |
| 3×95 | 5.5 | 3 | 66.6 | 5386 | 3655 | 0.193 | 0.32 |
| 3×120 | 5.5 | 3.1 | 69.4 | 6247 | 4058 | 0.153 | 0.253 |
| 3×150 | 5.5 | 3.2 | 72.9 | 7463 | 4757 | 0.124 | 0.206 |
| 3×185 | 5.5 | 3.3 | 76.8 | 8701 | 5292 | 0.0991 | 0.164 |
| 3×240 | 5.5 | 3.5 | 82.1 | 10519 | 6096 | 0.0754 | 0.125 |
| 3×300 | 5.5 | 3.7 | 87.3 | 12612 | 7068 | 0.0601 | 0.100 |
| 3×400 | 5.5 | 3.9 | 93.5 | 15634 | 8491 | 0.047 | 0.0778 |
| 3×500 | 5.5 | 4.1 | 101.4 | 19110 | 10044 | 0.0366 | 0.0605 |
| 3×630 | 5.5 | 4.3 | 109.8 | 23471 | 11699 | 0.0283 | 0.0469 |