Medium voltage N2XSEY cables for distribution networks;also for connection to generation units and plant and process connection.To be laid directly in ground,outdoors,indoors and in cable ducts.
IEC60228 Conductors of Insulated Cables
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV)up to 30kV(Um=36KV)-Part 2:Cables for Rated Voltages of 6kV(Um=7.2KV)up to 30kV (Um=36kV)
| No.of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight | Max.D.C.Resistance of Conductor at 20℃ | ||
| Cu | Al | Cu | Al | ||||
| mm² | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 3×50 | 8.0 | 3.2 | 70.3 | 4504 | 3641 | 0.387 | 0.641 |
| 3×70 | 8.0 | 3.3 | 74.2 | 5328 | 4079 | 0.268 | 0.443 |
| 3×95 | 8.0 | 3.4 | 78.2 | 6316 | 4585 | 0.193 | 0.320 |
| 3×120 | 8.0 | 3.5 | 81.0 | 7214 | 5024 | 0.153 | 0.253 |
| 3×150 | 8.0 | 3.6 | 84.5 | 8473 | 5768 | 0.124 | 0.206 |
| 3×185 | 8.0 | 3.7 | 88.4 | 9760 | 6352 | 0.0991 | 0.164 |
| 3×240 | 8.0 | 3.9 | 93.7 | 11648 | 7225 | 0.0754 | 0.125 |
| 3×300 | 8.0 | 4.0 | 98.7 | 13764 | 8221 | 0.0601 | 0.100 |
| 3×400 | 8.0 | 4.3 | 105.1 | 16911 | 9768 | 0.047 | 0.0778 |
| 3×500 | 8.0 | 4.5 | 113.0 | 20487 | 11421 | 0.0366 | 0.0605 |
| 3×630 | 8.0 | 4.7 | 121.4 | 24954 | 13182 | 0.0283 | 0.0469 |