Medium voltage N2XSRY cables for distribution networks.They are suitable for laying Indoor,tunnel,cable trench,shaft or buried laying,The cable can withstand mechanical external forces and a certain tensile force,it widely used in transformer stations,electric power plants and industrial plants.
IEC 60228 Conductors of Insulated Cables.
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from1kV (Um=1.2kV) up to 30kV (Um=36kV)-Part 2: Cables for Rated Voltages from 6kV (Um=7.2kV) up to 30kV (Um=36kV)
| No.of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Aluminum Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight | Max.D.C.Resistance of Conductor at 20℃ | ||
| Cu | Al | Cu | Al | |||||
| mm² | mm | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 1×50 | 8 | 2 | 2.2 | 38.6 | 1988 | 1702 | 0.387 | 0.641 |
| 1×70 | 8 | 2 | 2.2 | 40.3 | 2273 | 1858 | 0.268 | 0.443 |
| 1×95 | 8 | 2 | 2.3 | 42.3 | 2636 | 2062 | 0.193 | 0.32 |
| 1×120 | 8 | 2 | 2.3 | 43.5 | 2930 | 2204 | 0.153 | 0.253 |
| 1×150 | 8 | 2.5 | 2.4 | 46.4 | 3450 | 2552 | 0.124 | 0.206 |
| 1×185 | 8 | 2.5 | 2.5 | 48.3 | 3915 | 2785 | 0.0991 | 0.164 |
| 1×240 | 8 | 2.5 | 2.6 | 50.8 | 4574 | 3107 | 0.0754 | 0.125 |
| 1×300 | 8 | 2.5 | 2.6 | 53.2 | 5289 | 3450 | 0.0601 | 0.100 |
| 1×400 | 8 | 2.5 | 2.8 | 56.3 | 6295 | 3926 | 0.047 | 0.0778 |
| 1×500 | 8 | 2.5 | 2.8 | 59.9 | 7491 | 4484 | 0.0366 | 0.0605 |
| 1×630 | 8 | 2.5 | 3 | 64.2 | 9123 | 5219 | 0.0283 | 0.0469 |