Medium voltage N2XSRY cables for distribution networks.They are suitable for laying Indoor,tunnel,cable trench,shaft or buried laying.The cable can withstand mechanical external forces and a certain tensile force,it widely used in transformer stations,electric power plants and industrial plants.
IEC60228 Conductors of Insulated Cables.
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV)up to 30kV(Um=36kV)-Part 2:Cables for Rated Voltages of 6kV(Um=7.2kV)up to 30kV (Um=36kV).
| No.of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Aluminum Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight | Max.D.C.Resistance of Conductor at 20℃ | ||
| Cu | Al | Cu | Al | |||||
| mm² | mm | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 1×25 | 2.5 | 1.6 | 1.7 | 25.1 | 991 | 838 | 0.727 | 1.2 |
| 1×35 | 2.5 | 1.6 | 1.7 | 26.1 | 1114 | 903 | 0.524 | 0.868 |
| 1×50 | 2.5 | 1.6 | 1.8 | 27.4 | 1275 | 988 | 0.387 | 0.641 |
| 1×70 | 2.5 | 1.6 | 1.8 | 29.1 | 1522 | 1108 | 0.268 | 0.443 |
| 1×95 | 2.5 | 1.6 | 1.9 | 31.1 | 1838 | 1264 | 0.193 | 0.32 |
| 1×120 | 2.5 | 1.6 | 1.9 | 32.3 | 2099 | 1373 | 0.153 | 0.253 |
| 1×150 | 2.5 | 2.0 | 2.0 | 34.8 | 2587 | 1682 | 0.124 | 0.164 |
| 1×185 | 2.5 | 2.0 | 2.1 | 36.7 | 3000 | 1862 | 0.0991 | 0.125 |
| 1×240 | 2.6 | 2.0 | 2.2 | 39.4 | 3622 | 2148 | 0.0754 | 0.125 |
| 1×300 | 2.8 | 2.0 | 2.2 | 42.0 | 4283 | 2347 | 0.0601 | 0.100 |
| 1×400 | 3.0 | 2.5 | 2.4 | 46.7 | 5487 | 3111 | 0.047 | 0.0778 |
| 1×500 | 3.2 | 2.5 | 2.5 | 50.8 | 6648 | 3634 | 0.0366 | 0.0605 |
| 1×630 | 3.2 | 2.5 | 2.6 | 54.9 | 8155 | 4243 | 0.0283 | 0.0469 |