Medium voltage cables for distribution networks,also for connection to generation units and plant and process connection.To be laid directly in ground,outdoors,indoors and in cable ducts.
IEC 60228 Conductors of Insulated Cables.
Rated Voltages: from 6kV(Um=7.2kV) up to 30kV (Um=36kV)
| No.of Cores and Nominal Cross Section | Nominal insulation Thickness | Nominal Sheath Thickness | Approx Overall Diameter | Approx.Weight | Max.D.C. Resistance of Conductor at 20℃ | ||
| Cu | AI | Cu | AI | ||||
| mm² | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 1×25 | 2.5 | 1.5 | 17.1 | 495 | 342 | 0.727 | 1.20 |
| 1×35 | 2.5 | 1.5 | 18.1 | 603 | 391 | 0.524 | 0.868 |
| 1×50 | 2.5 | 1.6 | 19.4 | 744 | 457 | 0.387 | 0.641 |
| 1×70 | 2.5 | 1.6 | 21.1 | 966 | 552 | 0.268 | 0.443 |
| 1×95 | 2.5 | 1.7 | 23.1 | 1248 | 674 | 0.193 | 0.32 |
| 1×120 | 2.5 | 1.7 | 24.3 | 1493 | 766 | 0.153 | 0.253 |
| 1×150 | 2.5 | 1.8 | 26.0 | 1782 | 884 | 0.124 | 0.206 |
| 1×185 | 2.5 | 1.8 | 27.7 | 2153 | 1023 | 0.0991 | 0.164 |
| 1×240 | 2.6 | 1.9 | 30.4 | 2724 | 1257 | 0.0754 | 0.125 |
| 1×300 | 2.8 | 2.0 | 33.2 | 3351 | 1512 | 0.0601 | 0.1 |
| 1×400 | 3.0 | 2.1 | 36.5 | 4222 | 1853 | 0.047 | 0.0778 |
| 1×500 | 3.2 | 2.2 | 40.5 | 5290 | 2283 | 0.0366 | 0.0605 |
| 1×630 | 3.2 | 2.3 | 44.4 | 6693 | 288 | 0.0283 | 0.0469 |