Medium voltage NA2XSERY cables for distribution networks. They are suitable for laying indoor, tunnel, cable trench, shaft or buried laying. The cable can withstand mechanical external forces and a certain tensile force, it widely used in transformer stations, electric power plants and industrial plants.
IEC 60228 Conductors of Insulated Cables
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV) up to 30kV (Um=36KV) – Part 2: Cables for Rated Voltages of 6kV (Um=7.2KV) up to 30kV (Um=36kV).
| No.of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Steel Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight | Max.D.C.Resistance of Conductor at 20℃ | ||
| Cu | Al | Cu | Al | |||||
| mm² | mm | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 3×35 | 5.5 | 2.5 | 2.9 | 64.8 | 6432 | 5794 | 0.524 | 0.868 |
| 3×50 | 5.5 | 2.5 | 3 | 67.6 | 7082 | 6219 | 0.387 | 0.641 |
| 3×70 | 5.5 | 2.5 | 3.1 | 71.7 | 8126 | 6878 | 0.268 | 0.443 |
| 3×95 | 5.5 | 2.5 | 3.3 | 75.9 | 9298 | 7567 | 0.193 | 0.32 |
| 3×120 | 5.5 | 3.15 | 3.4 | 80.2 | 11273 | 9083 | 0.153 | 0.253 |
| 3×150 | 5.5 | 3.15 | 3.5 | 83.9 | 12756 | 10050 | 0.124 | 0.206 |
| 3×185 | 5.5 | 3.15 | 3.7 | 88 | 14332 | 10923 | 0.0991 | 0.164 |
| 3×240 | 5.5 | 3.15 | 3.8 | 93.3 | 16535 | 12112 | 0.0754 | 0.125 |
| 3×300 | 5.5 | 3.15 | 4.0 | 98.7 | 19055 | 13511 | 0.0601 | 0.100 |
| 3×400 | 5.5 | 3.15 | 4.2 | 105.1 | 22523 | 15381 | 0.047 | 0.0778 |
| 3×500 | 5.5 | 3.15 | 4.5 | 113.6 | 26767 | 17701 | 0.0366 | 0.0605 |
| 3×630 | 5.5 | 3.15 | 4.7 | 122.2 | 31814 | 20042 | 0.0283 | 0.0469 |