Home > Medium Voltage Power Cables > NA2XSERY Three Core 18/30 (36) kV Aluminum XLPE insulated Copper wire shielded Steel wire armored Cable
NA2XSERY Cable
NA2XSERY Cable

NA2XSERY Three Core 18/30 (36) kV Aluminum XLPE insulated Copper wire shielded Steel wire armored Cable

Application

Medium voltage NA2XSERY cables for distribution networks. They are suitable for laying indoor, tunnel, cable trench, shaft or buried laying. The cable can withstand mechanical external forces and a certain tensile force, it widely used in transformer stations, electric power plants and industrial plants.

Construction
  • Conductor: Aluminum, class 2, circular compacted conductors
  • Conductor screen: Non-metallic, semi-conducting compound
  • Insulation: Cross-linked Polyethylene (XLPE)
  • Insulation screen: Non-metallic, semi-conducting compound
  • Metallic screen: Copper wire
  • Filler: Non-hygroscopic material
  • Inner sheath: Polyvinyl chloride (PVC)
  • Armour: Steel wire
  • Outer sheath: Polyvinyl chloride (PVC)
Main Characteristics
  • Good electrical and mechanical properties.
  • Minimal dielectric loss, high insulation resistance.
Specification

IEC 60228 Conductors of Insulated Cables
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV) up to 30kV (Um=36KV) – Part 2: Cables for Rated Voltages of 6kV (Um=7.2KV) up to 30kV (Um=36kV).

Share:

Product Parameters

No.of Cores and Nominal Cross Section Nominal Insulation Thickness Nominal Steel Wire Diameter Nominal Sheath Thickness Approx. Overall Diameter Approx.Weight Max.D.C.Resistance of Conductor at 20℃
Cu Al Cu Al
mm² mm mm mm mm kg/km kg/km Ω/km Ω/km
3×50 8 3.15 3.5 81.1 9605 8742 0.387 0.641
3×70 8 3.15 3.6 85.2 10701 9453 0.268 0.443
3×95 8 3.15 3.7 89.2 11990 10259 0.193 0.32
3×120 8 3.15 3.8 92.2 13154 10964 0.153 0.253
3×150 8 3.15 3.9 95.9 14690 11985 0.124 0.206
3×185 8 3.15 4.1 100 16324 12916 0.0991 0.164
3×240 8 3.15 4.2 105.3 18603 14180 0.0754 0.125
3×300 8 3.15 4.4 110.7 21139 15595 0.0601 0.1
3×400 8 3.15 4.6 117.3 24818 17675 0.047 0.0778
3×500 8 3.15 4.8 125.4 29075 20009 0.0366 0.0605
3×630 8 3.15 5.1 134.2 34299 22527 0.0283 0.0469

Application and case display

FAQ

What are the benefits of EPR material?
What is the minimum order quantity for the product?
What is the application of Armored vs. Unarmored Cables?
Armored vs. Unarmored Cables?
What is the purpose of a metallic shield in MV and HV cables?
Longitudinal Water Blocking vs. Lateral Water Blocking?
A longitudinally water blocking cable is designed with a barrier to prevent the spread of moisture along its length. Longitudinal water blocking stops water from migrating along the cable's core, typically between the conductor strands, insulation layers, or metallic screens. Lateral water blocking ensures that water cannot penetrate the cable in the event that the sheathing is pierced or damaged. Radial water blocking prevents water from penetrating the cable's outer sheath or insulation layers, thereby stopping it from entering the cable structure entirely. Longitudinal water blocking can be achieved through various methods, including the application of water-blocking tapes and powders. These are frequently located on either side of a metallic screen and conductor. Lateral water blocking is typically accomplished by applying a layer of aluminum/polyester tape to the underside of the outer sheath.
What temperature can high-temperature resistant cables reach, and what are their application scenarios?
High-temperature resistant cables are engineered to function within a wide temperature range, spanning from -50°C to +260°C, depending on the cable's specific type and construction. Silicone rubber-insulated cables can withstand temperatures up to 180°C, whereas fluoroplastic insulated cables are designed to endure temperatures as high as 200°C to 260°C over extended periods. They are widely used in steel metallurgy, power, petrochemicals, aerospace, and industrial kilns for power transmission and equipment control in high-heat environments.
What is the application of Armored vs. Unarmored Cables?
Armored cables are suitable for use in hazardous environments, such as underground installations, areas with high moisture levels, and areas prone to mechanical damage. Unarmored cables are suitable for less demanding applications, such as inside walls or other protected locations.
What is the minimum order quantity for the product?
The minimum order quantity for low and medium voltage cables is 200 meters, whereas for high voltage cables, it is 2000 meters. Should the order quantity fall below the MOQ, however, if the factory has stock, we can still supply it.
What is the validity period for the offer of cable?
Typically, the offer is valid for 7 to 30 days, and the price will be adjusted according to the cost of raw materials and the exchange rate.

Get in Touch With Our Team

We're here to answer any questions you may have about our products, services, or technical specifications.
Address: No. 1207, Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou, China

    your Name

    your Email

    *

    Company Name

    *

    Country

    your Phone

    *

    WhatsApp No.

    Message

    *



    +86 371-63395670
    info@starsunelectric.com
    +86 13938540747
    Engineered for Excellence, Certified for Reliability – Power Cables That Meet IEC, ANATEL & INMETRO Standards Globally



      X