NA2XS(F)2Y Water-blocking medium voltage power cables are designed for distribution networks and generation units, and are suitable for external installation, includingdirect burial in the ground and in cable ducts.
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2kV) up to 30KV (Um=36kV) – Part 2: Cables for Rated Voltages of 6kV (Um=7.2kV) and 30kV (Um=36kV)
IEC 60228 specifies the nominal cross-sectional areas, in the range 0,5 mm2 to 3 500 mm2,for conductors in electric power cables and cords of a wide range of types.
| No.of cores x Nominal cross sectional area | Nominal Conductor Diameter | Nominal Insulation Thickness | Minimum Insulation Thickness | Nominal Sheath Thickness | Minimum Sheath Thickness | Nominal Overall Diameter | Nominal Weight | Conductor Dc Resistance At 20℃ |
| No. x mm² | mm | mm | mm | mm | mm | mm | Kg/km | ohms/km |
| 1×50/16 | 8.2 | 8 | 7.1 | 2 | 1.4 | 32 | 1000 | 0.641 |
| 1×70/16 | 9.7 | 8 | 7.1 | 2 | 1.4 | 34 | 1100 | 0.443 |
| 1×95/16 | 11.4 | 8 | 7.1 | 2.1 | 1.48 | 36 | 1300 | 0.32 |
| 1×120/16 | 12.65 | 8 | 7.1 | 2.1 | 1.48 | 37 | 1400 | 0.258 |
| 1×150/25 | 14.4 | 8 | 7.1 | 2.2 | 1.56 | 39 | 1600 | 0.203 |
| 1×185/25 | 15.75 | 8 | 7.1 | 2.2 | 1.56 | 41 | 1800 | 0.164 |
| 1×240/25 | 18.2 | 8 | 7.1 | 2.3 | 1.64 | 43 | 2000 | 0.125 |
| 1×300/25 | 20.5 | 8 | 7.1 | 2.4 | 1.72 | 46 | 2250 | 0.1 |
| 1×400/35 | 23 | 8 | 7.1 | 2.5 | 1.8 | 49 | 2750 | 0.0778 |
| 1×500/35 | 26 | 8 | 7.1 | 2.6 | 1.88 | 52 | 3250 | 0.0605 |
| 1×630/35 | 30.2 | 8 | 7.1 | 2.7 | 1.96 | 56 | 3750 | 0.0469 |