Medium voltage NA2XSRY cables for distribution networks. They are suitable for laying Indoor, tunnel, cable trench, shaft or buried laying. The cable can withstand mechanical external forces and a certain tensile force, it widely used in transformer stations, electric power plants and industrial plants.
IEC 60228 Conductors of Insulated Cables.
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV) up to 30kV (Um=36kV) – Part 2: Cables for Rated Voltages of 6kV (Um=7.2kV) up to 30kV (Um=36kV).
| No.of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal Aluminum Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight | Max.D.C.Resistance of Conductor at 20℃ | ||
| Cu | Al | Cu | Al | |||||
| mm² | mm | mm | mm | mm | kg/km | kg/km | Ω/km | Ω/km |
| 1×50 | 8.0 | 2.0 | 2.2 | 40.4 | 2109 | 1823 | 0.387 | 0.641 |
| 1×70 | 8.0 | 2.0 | 2.3 | 42.3 | 2407 | 1993 | 0.268 | 0.443 |
| 1×95 | 8.0 | 2.0 | 2.3 | 44.1 | 2748 | 2174 | 0.193 | 0.32 |
| 1×120 | 8.0 | 2.5 | 2.4 | 46.7 | 3214 | 2488 | 0.153 | 0.253 |
| 1×150 | 8.0 | 2.5 | 2.5 | 48.4 | 3664 | 2759 | 0.124 | 0.206 |
| 1×185 | 8.0 | 2.5 | 2.5 | 50.1 | 4104 | 2966 | 0.0991 | 0.164 |
| 1×240 | 8.0 | 2.5 | 2.6 | 52.8 | 4794 | 3320 | 0.0754 | 0.125 |
| 1×300 | 8.0 | 2.5 | 2.7 | 55.2 | 5504 | 3658 | 0.0601 | 0.1 |
| 1×400 | 8.0 | 2.5 | 2.8 | 58.3 | 6586 | 4210 | 0.047 | 0.0778 |
| 1×500 | 8.0 | 2.5 | 2.9 | 62 | 7773 | 4759 | 0.0366 | 0.0605 |
| 1×630 | 8.0 | 2.5 | 3.0 | 66.1 | 9370 | 5458 | 0.0283 | 0.0469 |