Home > Medium Voltage Power Cables > Primary UD 25kV Copper XLPE insulation Concentric Neutral LLDPE Cable
Primary UD Copper Cable
Primary UD Copper Cable

Primary UD 25kV Copper XLPE insulation Concentric Neutral LLDPE Cable

Application

Primary UD Cables are used in primary distribution network systems in residential, commercial and industrial areas. They can be used in conduit pipes, underground ducts or directly buried.

Construction
  • Conductor: Copper, circular compressed or compacted stranded conductors
  • Conductor screen: Non-metallic, semi-conducting compound
  • Insulation: cross-linked polyethylene XLPE or TRXLPE
  • Insulation screen: Non-metallic, semi-conducting compound
  • Metallic screen: Copper wires concentric neutral is with full or one-third
  • Outer sheath:Sunlight resistant,LLDPE
Main Characteristics
  • Maximum conductor temperature in normal operation: 90°C
  • Emergency overload temperature: shall not exceed 130°C
  • Short circuit temperature (5 seconds maximum duration ): shall not exceed 250°C
  • Product manufacturing options:Blocking elements against the penetration of water in the metallic part for humid and wet environments.
Specification

ASTM B 8 Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM B 496 Compact Round Concentric-Lay-Stranded Copper Conductors
ANSI/ICEA S-94-649 Concentric Neutral Cables Rated 5 Through 46kV

Share:

Product Parameters

Conductor Copper Neutral 100%  Insulation Level 133%  Insulation Level
Size Area Nominal Diameter No.of Wires Size Nominal  Insulation Thickness Nominal
Sheath
Thickness
Approx. Overall  Diameter Approx. Weight Nominal  Insulation Thickness Nominal  Sheath Thickness Approx.
Overall Diameter
Approx. Weight
AWG/kcmil mm² mm No. AWG mm mm mm kg/km mm mm mm kg/km
Full Neutral
1 42.4 7.59 13 12 6.60 2.03 33.7 1376 8.13 2.03 35.0 1525
1/0 53.5 8.53 16 12 6.60 2.03 34.7 1600 8.13 2.03 38.3 1748
2/0 67.4 9.55 13 10 6.60 2.03 36.8 1882 8.13 2.03 41.0 2068
3/0 85 10.7 16 10 6.60 2.03 38.0 2262 8.13 2.03 42.2 2463
4/0 107 12.1 20 10 6.60 2.03 39.3 2738 8.13 2.03 43.5 2909
1/3 Neutral
1 42.4 7.59 11 16 6.60 2.03 31.9 1146 8.13 2.03 35.0 1295
1/0 53.5 8.53 14 16 6.60 2.03 33.2 1317 8.13 2.03 36.8 1466
2/0 67.4 67.4 18 16 6.60 2.03 34.2 1510 8.13 2.03 38.4 1696
3/0 85 10.7 22 16 6.60 2.03 35.4 1763 8.13 2.03 39.6 1957
4/0 107 12.1 18 14 6.60 2.03 37.4 2113 8.13 2.03 41.6 2277
250 127 13.2 21 14 6.60 2.03 39.1 2388 8.13 2.03 42.7 2567
350 177 15.6 18 12 6.60 2.03 42.4 3073 8.13 2.79 47.8 3341
500 253 18.7 26 12 6.60 2.03 45.4 4218 8.13 2.79 50.8 4427
750 380 23.1 25 10 6.60 2.79 52.6 5989 8.13 2.79 57.0 6294
1000 507 26.9 32 10 6.60 2.79 57.7 7648 8.13 2.79 61.3 7909

Application and case display

FAQ

What is the application of Armored vs. Unarmored Cables?
How long is the validity period of cold shrink cable accessories?
Is a flame-retardant cable also fire resistant?
What is the purpose of a metallic shield in MV and HV cables?
Armored vs. Unarmored Cables?
What are the weight limits for different types of packages?
The weight limit for a wooden drum or steel wooden is 5,000 kg, and for a steel drum, it is 10,000 kg.
What is the purpose of a metallic shield in MV and HV cables?
Medium and high voltage power cables, typically those in circuits exceeding 2kV, usually feature a shield layer made of copper or aluminum tape. Similar to their use in low voltage cables, metallic wires and tapes are employed to prevent electromagnetic interference. These shields effectively neutralize or significantly diminish the field currents surrounding the conductor or core. The capacitive and inductive charging currents induced under normal operating conditions are subsequently grounded by the metallic screen.
Why do cable prices vary significantly among suppliers within the same region?
Cable prices vary due to differences in supplier strategies, competition, raw materials, and production processes, as well as after-sales services, including installation, equipment, and ongoing support.
What is the minimum order quantity for the product?
The minimum order quantity for low and medium voltage cables is 200 meters, whereas for high voltage cables, it is 2000 meters. Should the order quantity fall below the MOQ, however, if the factory has stock, we can still supply it.
What is the service life of cables?
The design life of power cables is typically 20 to 30 years; however, this can vary significantly based on factors such as installation, environmental conditions, and the quality of the cable.

Get in Touch With Our Team

We're here to answer any questions you may have about our products, services, or technical specifications.
Address: No. 1207, Building B, No. 96 Kangning Street, Zhengdong New District, Zhengzhou, China

    your Name

    your Email

    *

    Company Name

    *

    Country

    your Phone

    *

    WhatsApp No.

    Message

    *



    +86 371-63395670
    info@starsunelectric.com
    +86 13938540747
    Engineered for Excellence, Certified for Reliability – Power Cables That Meet IEC, ANATEL & INMETRO Standards Globally



      X