Medium voltage cables for distribution networks; also for connection to generation units, and for plant and process connections. To be laid directly in the ground, outdoors, indoors, and in cable ducts.
Note:
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1kV (Um=1.2KV) up to 30kV (Um=36KV) – Part 2: Cables for Rated Voltages of 6kV (Um=7.2KV) and 30kV (Um=36kV).
UNE HD 620 S3 Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6(7.2)kV to 20.8/36(42)kV.
| No.of Cores and Cross Section | Conductor Diameter | Nominal Insulation Thickness | Approx. Overall Diameter | Approx.Weight | D.C.Resistance of Conductor at 20℃ |
| mm² | mm | mm | mm | kg/km | Ω/km |
| 1×50/16 | 8.1 | 5.5 | 31 | 981 | 0.641 |
| 1×95/16 | 11.6 | 5.5 | 34.9 | 1267 | 0.32 |
| 1×150/25 | 14.3 | 5.5 | 38.2 | 1634 | 0.206 |
| 1×240/25 | 18.3 | 5.5 | 42.2 | 2042 | 0.125 |
| 1×400/35 | 23.2 | 5.5 | 47.1 | 2722 | 0.0778 |